The CleanAirTower hall ventilation and room ventilation is used wherever point extraction of welding fumes is not sufficient. The tower effectively protects employees and machines from fine dust during welding. The cleaned air is fed back into the room. The new optimised air flow has a special effect and, similar to the principle of the pinball, ensures that possible sparks and particles collide with metal sheet elements at 10 or more points, thus effectively removing energy from them. The hall ventilation causes only minimal air turbulence, which is why the polluted air does not reach unpolluted areas.
Filter stages
1
Filter method
Cleanable filter
Filter cleaning method
Rotating nozzle
Filter surface
20 m²
Number filter elements
3
Filter surface total
60 m²
Filter material
PTFE-membrane
Filter efficiency
> 99.9 %
Dust classification
M
Extraction capacity
6000 m³/h
Height
3617 mm
Diameter
1172 mm
Weight
666 kg
Motor power
5.5 kW
Power supply
3 x 400 V / 50 Hz
Rated current
11 A
Control voltage
24 V, DC
Noise level
72 dB(A)
Fan type
Radial fan, direct driven
Compressed air supply
5 - 6 bar
Capacity Dust collection container
10 l